BEDROOM LIGHTING
The bare minimum
The following is an outline of basic requirements for a three-bedroom house with 120m2 floor area. This would be a typical speculative estate development.
* Rooms: small kitchen; dining room; lounge; downstairs cloakroom; main bedroom with en-suite bathroom; second double bedroom; small single bedroom; landing bathroom or shower room;
*Heating: central heating by gas or oil;
*Garden: small garden at both front and rear.
Standards
National House Building Council (NHBC)
The NHBC give minimum standards for living accommodation and services, which are shown in It should be noted that houses vary in size and use, so the values given should be considered as a minimum.
Relevant wiring regulations
13 A socket-outlets
* Building Regulations now require socket-outlets, wall switches and other similar accessories to be sited in habitable rooms at appropriate heights of between 450 and 1200mm from the finished floor levels.
*Any socket-outlet with a rated current not exceeding 20 A, which is used by ordinary persons’ equipment for use outdoors must be provided with additional protection by means of a 30mA RCD.
*No 230V sockets, except shaver sockets complying with BS EN 61558-2 are permissible in bathrooms and shower rooms.
* 230V socket-outlets must be located at least 3m outside the boundary of zone 1 and provided with 30mA RCD protection.
Lighting
*To avoid danger and inconvenience, there should be more than one lighting circuit.
* In a bathroom, all equipment must be suitable for the zone in which it is installed.
*Wall switches and other accessories must not be installed in zones 0, 1 and 2.
* Cord switches must be installed outside of zones 0, 1 and 2, but the cord may hang within zones 1 and 2.
*There are restrictions on the current-using equipment in zones 0, 1 and 2.
* Equipment that is installed in zones 1 and 2 must have water penetration protection of at least IPX4.
*A careful study of BS 7671: 2008 Section 701 is recommended.