Earth resistance is measured with a Megger (earth tester) by driving auxiliary electrodes into the ground and applying a test current through them. The Megger then measures the voltage drop and calculates resistance (Ohm’s Law: R = V/I).
Detailed Technical Explanation:
1. Principle:
Earth resistance testing involves passing a known current through the soil between the earth electrode under test and an auxiliary electrode, then measuring the potential difference between them.
Using Ohm’s law (R = V/I), the resistance of the earth electrode system is determined.
2. Setup with Megger (3-point or 3-terminal method):
- Disconnect the earth electrode under test from the installation.
-Place two auxiliary electrodes (rods) in a straight line:
• Current electrode (C): Driven into the ground about 30–50 meters away from the test electrode.
• Potential electrode (P): Placed between the test electrode and current electrode, usually at 10–15 meters distance.
- Connect the Megger terminals:
• E (Earth): To the electrode under test.
• P (Potential): To the potential electrode.
• C (Current): To the current electrode.
3. Testing Process:
- The Megger injects a small AC current (to avoid polarization of soil) between the earth electrode and the current electrode.
- It measures the voltage drop between the earth electrode and the potential electrode.
- The instrument then calculates Earth Resistance = Voltage / Current and displays it in ohms (Ω).
4. Good Practices:
- Ensure the soil is moist for proper measurement.
- If resistance readings fluctuate, reposition the auxiliary electrodes further apart.
- For verification, move the potential electrode slightly forward and backward (10% distance each side). Consistent readings mean accurate results.
5. Acceptable Values:
- General installations: < 5 Ω
- Power stations, substations, and sensitive equipment: ideally < 1 Ω
Here's the diagram:
E → Earth electrode under test
P → Potential electrode (placed in between)
C → Current electrode (placed further away)
Megger → Connected to all three points (E, P, C) to inject current and measure resistance.
This setup ensures accurate measurement of the resistance of the earth electrode system.
Final Summary:
To check earth resistance with a Megger, you isolate the earth electrode, drive two auxiliary rods into the soil, connect them to the tester (E, P, C), and let the Megger pass a current and measure the voltage drop. The displayed resistance indicates the quality of earthing — the lower the resistance, the safer and more effective the earthing system.
No comments:
Post a Comment